PROmesh P10X Managed Switch/ IP 67

Item #114110210 – PROmesh P10x – IP67 10-Port PROFINET and EtherNet

    • For use outside the control cabinet
    • Space-saving thanks to a compact design
    • Shorter cable routes / more space in the control cabinet
    • Simplified maintenance thanks to innovative monitoring functions (with alarm)
    • Suitable for extreme temperatures (-40 to +75 °C)
    • Suitable for welding applications (thanks to metal housing)
    • Suitable for moving plant sections (vibration-resistant)

Need assistance?

Call: +46 (0)40 636 8038 

Email:  brian@old.lindhautomation.com

PROmesh P10X: Features in Detail

Webinterface view of the PROmesh P10X Cable Diagnostics

Online Cable Diagnostics (during operation)

 

Detect and rectify line-based defects at an early stage!

The PROmesh P10X brings innovative online cable diagnostics into the IP67 range of your systems and machines, making it possible to visualize the physical wear of your network cables permanently.

Achieved by a complex evaluation system that compares the current value of connected data cables with a set value corresponding to the cable length. The determined quality value (“Q-value”) is indicated clearly for each port.

Unlike other cable testers, the PROmesh P10X performs the cable diagnosis continuously and during ongoing system operation. The innovative online cable diagnosis combined with the powerful industrial switch (IP67) makes this possible. Thanks to this permanent monitoring, critical cable conditions can be automatically detected and remedied by your maintenance department – before your system operation is impaired!

 

MONITORING FUNCTIONS (with event notification)  Simplified maintenance thanks to early detection

Detect abnormalities in the network and data communication at an early stage. Maintenance work can be carried out in a more targeted and planned manner – before faults or failures occur. Relieve your maintenance staff and stabilize your system operation permanently.

 

PERFORMANCE MONITORING  Identify Network Load Bottlenecks

Since data traffic volume varies at different points in an industrial network, it is advisable to monitor the network load at important data nodes (=switches). If the data traffic exceeds the switch’s capacity, data loss (discards) or communication disruptions occur.

Often these sporadic network load peaks occur due to acyclic data queries or TCP/IP applications. To make these short-term overloads visible, the PROmesh P10X provides network load statistics. The statistics show all network loads per port and discards that have occurred, up to the second, enabling performance-related bottlenecks to be discovered and eliminated.

 

EMC MONITORING  Equipotential Bonding Ok?

Having communication errors or interruptions? Despite correct shielding, EMC coupling in data lines occurs again and again in practice. To better detect these sources of EMC interference, the PROmesh P10X has permanent leakage current monitoring.

The integrated leakage current monitoring of the PROmesh P10X records the frequency and intensity of occurring EMC disturbances in addition to the exact time. The precise moment of the event is recorded and stored to simplify the search for the interference source. Viewing the snapshot is effortlessly done via the integrated web interface.

The automatic alarm notification gets sent if a value exceeds the freely set limit.

 

VOLTAGE MONITORING (24 V)  Over/Under Voltage Present ?

Switching components and loads on and off can cause voltage fluctuations to occur in the system. These over/under voltages can damage or cause failures of switches and other components.

In the case of switches, with the central communication nodes such failures are particularly critical as the system communication would be considerably affected. For this reason, the PROmesh P10X has integrated monitoring of the power supply (24 V) that can be integrated into your central network monitoring as an additional stability parameter.

 

TEMPERATURE MONITORING  Safety Despite Extreme Conditions

The extended temperature range (-40 to +75 °C) allows the PROmesh P10X to be used even under extreme environmental conditions. The integrated monitoring of the device temperature provides additional safety during use.

Additionally, the thermal wear of the switch can also be tracked and reduced. The integrated web interface allows for the management of the individual tolerance range of the temperature alarm.

 

All relevant condition values at a glance:

Better plant availability without additional inspection efforts

Modern plants and machines are network-based. The condition of your network reveals an enormous amount about the available reserves of your system. Tracking the health of the network makes it possible to secure or even increase plant availability. Make the status of your (sub)network visible at any time with the PROmesh P10X.

 

CLEAR USER INTERFACE (According to Traffic Light Color Scheme)

Condition and measurement values only help if you can use them in an simplified way. For this reason, the PROmesh P10X’s integrated web interface records the monitoring and diagnostic data (and it is recorded) and can then be easily viewed on or off-site for review.

Speed up routine condition checks with the proven condition evaluation – based on the traffic light principle (red, yellow, and green). Additionally, all measured values are graphically processed and clearly displayed, allowing anomalies or a need for action to be recognized with ease.

 

EVENT ALARMS WITH PUSH NOTIFICATION (Individually Customizable)

The alarm manager of the PROmesh P10X documents all events and abnormalities down to the millisecond regardless of preset, according to Indu-Sol’s recommendation, or individual value. Detect and eliminate potential sources of interference, preventatively, with automated notifications triggered by events, depending on the configuration.

The following notifications are supported:

  • PN-RTA
  • SNMP
  • E-mail
  • Relay

 

IP67 certified (water/dust resistant)Developed for the harshest operating conditions

IP67 Rated PROmesh P10X Industrial Ethernet Switch

Thanks to its robust and compact design, the PROmesh P10X is well suited for use outside the control cabinet. Effortlessly implement sophisticated network structures – optional to mount directly on robots or other moving system parts.

≫ For use outside the control cabinet

≫ Space-saving thanks to the compact design

≫ Suitable for extreme temperatures (-40 to +75 °C)

≫ Suitable for welding applications (thanks to metal housing)

≫ Suitable for moving plant sections (vibration-resistant)

 

Gigabit-capable (up to 1 GBit/s) , PROFINET v2.4 – Solid switch performance that does not shy away from comparison

In addition to the advanced maintenance-friendly functions, the PROmesh P10X impresses with its performance as an Industrial Switch (IP67) for PROFINET and Industrial Ethernet. It combines network performance and diagnostics – without the need for additional measuring devices in the network section.

≫ 8 port x 100 Mbps; 2 port x 1.0 GBps

≫ Netload Class III

≫ Conformance Class B

≫ Support of several ring protocols (MRP, STP, RSTP)

 

MORE BANDWIDTH FOR HETEROGENEOUS/CONVERGENT NETWORKS – BUT HOW?

Due to the higher communication traffic volume, heterogeneous or convergent networks require more bandwidth. There are two primary approaches to increase the usable bandwidth in the industrial environment:

The following notifications are supported:

≫ Increase the actual bandwidth (Gigabit communication)
by increasing the data rate to 1 Gbps or more
Note: Devices, applications, and cables must be Gigabit-capable

≫ Increase of the usable bandwidth (TSN communication)
through improved real-time communication and data prioritization
Note: Devices and applications must be TSN-compatible